PYN, SPYN CORTEM

Sockets and plugs from 16 A to 125 A

The PYN, SPYN series of sockets and plugs consists of 16 A and 32 A models and 63 A and 125 A models designed with ‘Ex db eb, Ex tb’ and ‘Ex eb, Ex tb’ protection and tested for operation at low temperatures down to -60°C. The range includes two pole sockets + earth (PE); three pole sockets + earth (PE) and three pole sockets + neutral + earth (PE), with current capacities of 16A and reduced overall dimensions, up to a maximum of 125A. Voltages range from 50V to a maximum of 690VAC, with a maximum frequency of 50/60Hz.

KEY FEATURES:

  1. Group IIC
  2. Zone 1, 2, 21, 22
  3. Aluminium alloy
  4. Plugs can be used with industrial sockets

Socket body in low copper content aluminium alloy, complete with wall fastening lugs and plastic bayonet socket closure cap, with identifying colour and safety chain. Plug body in low copper content aluminium alloy, complete with colour coded plastic lock rings to identify the mains power supply voltage. Screw fastened lid, aluminium alloy with low copper content. Used to access socket and make electrical connection. Pins in nickel-plated brass. Silicone gasket.


TECHNICAL SPECIFICATIONS:

CERTIFICATE DATA

Classification: Group II Category 2GD

Installation: EN 60079.14 zone 1 – zone 2 (Gas) zone 21 – zone 22 (Dust)

Marking: II 2 GD Ex db eb IIC T… Gb; Ex tb IIIC T…°C Db Socket

II 2 GD Ex eb IIC T… Gb; Ex tb IIIC T…°C Db Plug

Certificate: ATEX IMQ 20 ATEX 049X

IEC Ex IMQ 21.0003X For all IEC Ex certificate data, download the

certificate from www.cortemgroup.com

Standards:

CENELEC EN 60079-0: 2018, EN 60079-1: 2014, EN 60079-7: 2017, EN 60079-31: 2014

and European Directive 2014/34/EU.

IEC 60079-0: 2017, IEC 60079-1: 2014, IEC 60079-7: 2017, IEC 60079-31: 2022

RoHS Directive 2002/95/EC.

Models: 16 A 32 A

Temperature class: T85°C (T6) T100°C (T4)

Temp. Temperature: -60°C +60°C -60°C +60°C

Models: 63 A 125 A

Temperature class: T85°C (T6) T140°C (T3) T134°C (T4)

Temp. Temperature: -60°C +60°C -60°C +55°C -60°C +49°C

Degree of protection: IP66

ELECTRICAL FEATURES

Rated voltage: Max. 690 V

Rated frequency: Max. 50/60 Hz

Rated current: 16 A, 32 A, 63 A and 125 A

Cable entry: no. 2 on the socket and no. 1 on the plug

Max. cable cross-section: for 16A: 4 mm2 for 63 A: 10 – 16 mm2

for 32A: 6 mm2 for 125 A: 35 – 50 mm2

 