Zirconia oxygen probe – ZFK8 FUJI ELECTRIC

The probe is used for continuous measurement of oxygen concentration in flue gases from boilers and industrial furnaces, for combustion control and optimization. It consists of a measurement probe combined with a signal converter. The probe is associated with a convection tube which is inserted into the flue gas to channel the gases to the probe for oxygen measurement. The converter (ZKM) is a microprocessor-based signal converter that manages inputs/outputs, digital communication, display and control of the overall operation. The converter features advanced functions such as self-diagnosis of operation and probe regeneration, giving it very long stability.

Features

  • • No gas conditioning system required
    • Easy maintenance
    • High reliability thanks to diagnostic function
    • Safe and secure
    • Easy to use
    • HART® communication is available as an option

Fields of application

Ideal for combustion control in boilers, incinerators and furnaces.


Technical Specifications:

Measured gas temperature Convection tube system :
-10 °C to +600 °C (for general use, corrosive gases)
System with ejector :
-10 °C to 1500 °C (for high-temperature gases)
-10 °C to +800 °C (general purpose)
Measured gas pressure -3 to +3 kPa (-306 to +306 mm H2O)
Operating temperature – 10 °C to +60 °C for the detector head
-5 °C to +100 °C for the ejector
≤ 125 °C on detector flange, under voltage
Storage temperature -20 °C to +70 °C for the sensing element
-10 to +100 °C for the ejector
Construction Waterproof and dustproof (IEC IP66)
Filter Alumina (porosity: 50 µm) and quartz paper
Main materials of parts in contact with gas Detector: Zirconium, 316 stainless steel, platinum
Convection tube: 316 stainless steel
Standard ejector: 316 stainless steel, 304 stainless steel
High-temperature ejector: SiC, stainless steel 316, stainless steel 304
Calibration gas inlet 6 mm tube or 1/4″ tube (according to datasheet )
Calibration gas flow 1.5 to 2 l/min
Detector mounting ± 45° from horizontal, the ambient air must be
be clean
Ejector air inlet flow rate 5 to 10 l/min
Purge air inlet pressure 200 to 300 kPa (2 to 3 kgf/cm2)
Finish color Silver and steel color
Exterior dimensions (L x Ø max) 210 mm x 100 mm
Approximate weight Detector: 1.6 kg
Ejector: 15 kg (with 1 m tube)
Standard 1 m convection tube: 5 kg

 